Wire Gauge Reference: 14, 12 & 10 AWG Copper

For ordinary applications under NEC 240.4(D), the general copper small-conductor overcurrent limits are 15 A for 14 AWG, 20 A for 12 AWG, and 30 A for 10 AWG. These limits are not a complete wire-sizing calculation.

Scope: 14–10 AWG copper only; 2023 NEC reference. General small-conductor protection limits, subject to specific code exceptions. Aluminum, cable assembly rules, correction factors, and load calculations are outside this lookup.

Choose a wire gauge

Free · No sign-up

Your reference result

20 A general overcurrent limit

12 AWG copper · NEC 240.4(D). Bare solid diameter is approximately 0.080 in. Check installation conditions and load requirements separately; this is not a wire-sizing approval.

Quick reference

Copper small-conductor reference · NEC 240.4(D)
GaugeGeneral overcurrent limitApprox. solid conductor diameter
14 AWG15 A0.064 in
12 AWG20 A0.080 in
10 AWG30 A0.101 in

Before you use the result

  • A 75°C or 90°C ampacity column does not by itself allow a larger breaker for these small conductors.
  • Check load, continuous-load requirements, termination ratings, wiring method, ambient temperature, conductor grouping, voltage drop, and equipment instructions before choosing a conductor.
  • Diameter is bare solid copper, not the outside diameter of insulated cable. Do not use it to size conduit.

Sources & edition notes

This is an independent HandySuite reference. The linked publisher’s code or equipment documentation governs the work.

Common questions

What gauge copper wire is commonly associated with a 20 A circuit?

12 AWG copper has a general 20 A small-conductor protection limit. That is a starting reference, not confirmation that it suits the actual load, installation, or run length.

Can I use the same limits for aluminum?

No. This reference is limited to copper. Aluminum has different rules and connection requirements.